Spares / Spares by Brand / DSE Deep Sea Electronics / DSE Generator Control Modules

DSE8620 MKII Load Sharing & Synchronising Control Module

On Sale!
$4,180.00$3,845.00 inc GST($3,495.45 ex GST)
The Macfarlane Advantage
  • Oil
  • Run-Up
  • Load Tested
Every generator we sell is:
  • Filled with oil at no extra cost
  • Run & load tested to rated capacity
  • Ready to use as soon as you receive it
Trust your generator with Macfarlane Generators, a real generator company that has been operating for 70+ years.

We stock a full range of spares, run a full service department, have stores across Australia and employ an experienced team with extensive generator knowledge

We provide the best generator sales and after-sales support in Australia.

Synchronising & Load Sharing Auto Mains (Utility) Failure Control Module.

The DSE8620 is an intelligent mono display auto mains (utility) failure load share control module packed with industry leading features to enhance paralleling single gensets with a mains (utility) supply.

The DSE 8620 automatically controls the change over between mains (utility) and generator power and can also be configured to run a generator in synchronisation with a mains (utility) supply.

Details
 
  • Overall Size: 240 mm x 181 mm x 42 mm (9.4” x 6.8” x 1.6”)     
  • Panel Cutout Size: 220 mm x 160 mm (8.7 " x 6.3")
  • Maximum Panel Thickness: 8.0 mm (0.3”)     
  • Weight: 0.88kg
  • Product Variants
    8620-01 - 8620 Auto Mains (Utility) Failure Control Module

Specifications
DC SUPPLY

Continuous Voltage Rating
8 V to 35 V Continuous
Cranking DropoutsAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. 
Maximum Operating Current460 mA at 12 V, 245 mA at 24 V
Maximum Standby Current375 mA at 12 V, 200 mA at 24 V
Charge Fail/Excitation Range0 V to 35 V
OUTPUTS
Output A (Fuel)15 A DC at supply voltage
Output B (Start)15 A DC at supply voltage
Outputs C & D8 A 250 V (Volt free)
Auxiliary Outputs E, F, G, H, I & J2 A DC at supply voltage
GENERATOR & MAINS
Voltage Range15 V to 333 V AC (L-N)
Frequency Range3.5 Hz to 75 Hz
MAGNETIC PICK UP
Voltage Range+/- 0.5 V to 70 V
Frequency Range10,000 Hz (max)
BUILT IN GOVERNOR AND AVR CONTROL
Minimum Load Impedance1000Ω
Fully isolated
Gain Voltage0 V to 10 V DC
Fully isolated
Offset Voltage+/- 10 V DC
Fully isolated